Pin Connections for Cabling Between APC UPS and RS-232

Last reviewed: May 6, 1997
Article ID: Q98885
The information in this article applies to:
  • Microsoft Windows NT operating system version 3.1

SUMMARY

If you are having difficulty getting your American Power Conversion (APC) uninterruptable power supply (UPS) system to work with Windows NT, it may be due to the serial cable you are using. The following information applies to APC Back-Ups models 250, 400, 450, 600, 900, and 1250.

Make sure the following pins are connected:

   DB9 9-Pin Female Connector              DB9 9-Pin Male Connector
      (to PC serial port)                    (to UPS connector)
   ----------------------------------------------------------------
      Pin #5----------Ground------------------Pin #4
      Pin #8----------Power Failure-----------Pin #2
      Pin #4----------UPS Shutdown------------Pin #1
      Pin #1----------Low Battery---------Pin #5--[10k ohm]--Pin #8

Note: unlisted pins need not be connected.

MORE INFORMATION

APC provides a cable that correctly connects their power supply unit to a PC. You can contact APC and order part #940-0020B.


Additional query words: prodnt
Keywords : kbhw ntfault nthw
Version : 3.1
Platform : WINDOWS


THE INFORMATION PROVIDED IN THE MICROSOFT KNOWLEDGE BASE IS PROVIDED "AS IS" WITHOUT WARRANTY OF ANY KIND. MICROSOFT DISCLAIMS ALL WARRANTIES, EITHER EXPRESS OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL MICROSOFT CORPORATION OR ITS SUPPLIERS BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF MICROSOFT CORPORATION OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES SO THE FOREGOING LIMITATION MAY NOT APPLY.